1 1 vote The single line diagram of a balanced power system is shown in the figure. The voltage magnitude at the generator internal bus is constant and $1.0$ p.u. The p.u. reactances of different components in the system are also shown in the figure. The infinite bus voltage magnitude is $1.0$ p.u. A three phase fault occurs at the middle of line $2$. The ratio of the maximum real power that can be transferred during the pre-fault condition to the maximum real power that can be transferred under the faulted condition is _________. Power Systems gate2016-ee-2 single-line-diagram three-phase-fault pre-fault-condition numerical-answers + – Misbah Ghaya 374 views answer comment Share Follow 0 reply Please log in or register to add a comment.