A $30$ kV, $50$ Hz, $50$ MVA generator has the positive, negative, and zero sequence reactances of $0.25$ pu, $0.15$ pu, and $0.05$ pu, respectively. The neutral of the generator is grounded with a reactance so that the fault current for a bolted LG fault and that of a bolted three-phase fault at the generator terminal are equal. The value of grounding reactance in ohms (round off to one decimal place) is ___________
edited by

Please log in or register to answer this question.

Answer: